How to calculate box fill (NEC 314.16)

Count every conductor, ground, clamp and device in cubic inches, then compare with the box.

The short answer

Add up the volume each item takes in cubic inches and compare it with the box's volume (NEC 314.16). Each conductor counts its size's allowance: 2 in³ for 14 AWG, 2.25 for 12 AWG, 2.5 for 10 AWG. A device yoke counts two of the largest conductor connected to it; all equipment grounding conductors together count one; internal clamps count one.

Step by step

  1. Count each insulated conductor that enters the box and is spliced or terminated there, or passes through it, once at its own size's allowance; an unbroken loop of 12 inches or more counts twice.
  2. Add one allowance for all equipment grounding conductors together, sized by the largest of them, plus a quarter allowance for each one beyond four.
  3. Add one allowance of the largest conductor in the box if it has internal cable clamps, and one for each type of support fitting, such as fixture studs or hickeys.
  4. Add two allowances of the largest conductor connected to each device yoke (a receptacle or switch).
  5. Compare the total with the box's marked volume or its Table 314.16(A) volume; the box fits if its volume is at least the total.

Worked example

A receptacle fed by two 12/2 cables with ground in a box with internal clamps: four 12 AWG conductors, two equipment grounding conductors and one device yoke need 18 in³. The smallest standard boxes that hold it are 3 x 2 x 3-1/2 device and 4 x 1-1/4 square (18 in³).

ItemCountEachVolume
12 AWG conductors42.25 in³9 in³
Internal cable clamps12.25 in³2.25 in³
Device yokes (2 each)22.25 in³4.5 in³
Equipment grounding conductors12.25 in³2.25 in³

Volume per conductor (Table 314.16(B)(1))

ConductorVolume
14 AWG2 in³
12 AWG2.25 in³
10 AWG2.5 in³
8 AWG3 in³
6 AWG5 in³

Standard metal boxes (Table 314.16(A))

Maximum counts assume conductors only, no devices, clamps or grounds.
BoxVolumeMax 12 AWGMax 14 AWG
4 x 1-1/4 round/octagonal12.5 in³56
4 x 1-1/2 round/octagonal15.5 in³67
4 x 2-1/8 round/octagonal21.5 in³910
4 x 1-1/4 square18 in³89
4 x 1-1/2 square21 in³910
4 x 2-1/8 square30.3 in³1315
4-11/16 x 1-1/4 square25.5 in³1112
4-11/16 x 1-1/2 square29.5 in³1314
4-11/16 x 2-1/8 square42 in³1821
3 x 2 x 1-1/2 device7.5 in³33
3 x 2 x 2 device10 in³45
3 x 2 x 2-1/4 device10.5 in³45
3 x 2 x 2-1/2 device12.5 in³56
3 x 2 x 2-3/4 device14 in³67
3 x 2 x 3-1/2 device18 in³89
4 x 2-1/8 x 1-1/2 device10.3 in³45
4 x 2-1/8 x 1-7/8 device13 in³56
4 x 2-1/8 x 2-1/8 device14.5 in³67

Common mistakes

  • Counting each equipment grounding conductor separately: together they count one allowance (plus a quarter for each beyond four).
  • Forgetting the device yoke: a receptacle or switch takes two allowances of the largest conductor connected to it.
  • Counting pigtails and wire connectors: a conductor that starts and ends inside the box, and small fittings such as wire connectors, are not counted.
  • Leaving out ring and cover volume, or counting it unmarked: plaster rings, extension rings and domed covers add to the box's volume only when they are marked with their volume or made from a box in Table 314.16(A).

Code numbers and editions

Section numbers here are NEC 2023's, which most states enforce. Conductors larger than 6 AWG are sized for pull and junction boxes under 314.28, not by volume.

Code adoption cycles change. Always confirm the edition and amendments in force with your Authority Having Jurisdiction (AHJ) before permitting work.